「英中对照」荷兰兹沃勒省府办公楼采用丹佛斯数字执行器改造无燃气暖通系统
Digital Actuators Optimize HVAC for Gas-Free Building
荷兰上艾瑟尔省兹沃勒的省政府办公楼已完成无燃气暖通系统改造,采用丹佛斯压力无关控制阀、数字执行器、自然冷媒热泵及楼宇自控系统。改造保留建筑原有散热器、对流器等末端设备,配套楼宇管理平台可根据人员实际占用情况自动调节暖通,支持楼层级能耗、占用状态与运行数据可视化。
材料披露荷兰兹沃勒省府办公楼无燃气暖通改造的技术路径与项目方公布的运行效果,相关节能、舒适度数据未经过独立验证,需核验测试基准及长期运行表现。
Case studies
smartbuildingmag.com
10 {{ "2026-10-10T00:00:00+00:00" | date "MMM" }} '26
Written on {{ "2026-10-10T00:00:00+00:00" | date "longDate" }} Modified on {{ "2026-10-10T00:00:00+00:00" | date "longDate" }}
The province of Overijssel collaborated with Danfoss to implement a data-driven, gas-free HVAC system in its provincial government building in Zwolle.
www.danfoss.com

The Provinciehuis Overijssel in Zwolle, the Netherlands, was built in 1972 as one of the first regional government facilities to feature large open-plan workspaces accommodating approximately 1,000 employees. To support the region's ambition to become completely energy-neutral, the building management needed to transition from a traditional climate control system utilizing gas-fired boilers and low-temperature heat pumps to a fully gas-free setup. A major technical challenge was the requirement to execute this transition without major structural modifications, specifically aiming to retain the existing terminal units such as radiators, convectors, and ceiling induction units. These existing legacy units required higher supply temperatures, complicating the integration of a sustainable heating solution.
Implementing data-driven digital control technology
The facility faces widely varying occupancy levels due to hybrid working arrangements, making it critical to accurately monitor and automatically optimize energy consumption and climate control. Furthermore, regional regulations mandated the implementation of a Building Automation and Control System to reduce energy consumption and improve operational efficiency. To meet these demands, the installation company Heijmans and smart-building specialist bGrid collaborated with Danfoss to deploy a future-ready technical solution. The gas-fired central heating boilers were replaced with a heat pump utilizing natural refrigerants. To control the hydronic ceiling units precisely, the engineering team integrated Danfoss pressure-independent control valves combined with digital actuators. This configuration creates a dynamically balanced and self-optimizing HVAC network capable of handling fluctuating thermal loads.

Reduced energy consumption and operational insights
Data from the smart sensors and controllers is collected, stored, and visualized through a dedicated building management platform. This infrastructure provides building managers with floor-level insights into space occupancy, energy use, and system performance, allowing the climate control system to automatically respond to actual room usage. The deployment of this smart digital control architecture has yielded measurable operational results. The modernized system consumes approximately one-third of the energy required by the former gas boiler setup, resulting in a reduction of 200,000 kWh of gas energy annually alongside a 10 percent decrease in electricity costs. Matching equipment performance to actual occupancy, such as shutting down climate control on unused floors during low-attendance days, cuts energy consumption by more than 25 percent. Additionally, indoor comfort improved significantly, reflected in an 80 percent reduction in climate-related complaints, while operators gained the ability to continuously monitor deviations and maintain optimal indoor air quality.
Edited by Maria Brueva, Induportals editor – adapted by AI.
www.danfoss.com
来源:Smart Building International · smartbuildingmag.com