Brick Schema 官方版本发布· gtfierro·· 2024-04-15AI 评分69

Brick Schema发布v1.4.0版本 明确楼宇自控实体弃用替换与跨Schema迁移规则

v1.4.0

AI 导读

Brick Schema官方发布v1.4.0版本,同步公布该版本及此前版本弃用实体的替换映射规则。该版本中REC ICT类正逐步弃用并替换为对应Brick类,Brick位置类正逐步弃用并替换为RealEstateCore对应类。其余变更包括水系统测点命名调整、暖通相关类重命名及部分定义不清类的替换或移除。

正文
{
  "https://w3id.org/rec#BACnetController": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:BACnetController",
    "replacement": "https://brickschema.org/schema/Brick#BACnet_Controller"
  },
  "https://w3id.org/rec#Controller": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:Controller",
    "replacement": "https://brickschema.org/schema/Brick#Controller"
  },
  "https://w3id.org/rec#DataNetworkEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:DataNetworkEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Data_Network_Equipment"
  },
  "https://w3id.org/rec#DaylightSensorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:DaylightSensorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Daylight_Sensor_Equipment"
  },
  "https://w3id.org/rec#EthernetPort": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:EthernetPort",
    "replacement": "https://brickschema.org/schema/Brick#Ethernet_Port"
  },
  "https://w3id.org/rec#EthernetSwitch": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:EthernetSwitch",
    "replacement": "https://brickschema.org/schema/Brick#Ethernet_Switch"
  },
  "https://w3id.org/rec#IAQSensorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:IAQSensorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#IAQ_Sensor_Equipment"
  },
  "https://w3id.org/rec#LeakDetectorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:LeakDetectorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Leak_Detector_Equipment"
  },
  "https://w3id.org/rec#ModbusController": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:ModbusController",
    "replacement": "https://brickschema.org/schema/Brick#Modbus_Controller"
  },
  "https://w3id.org/rec#NetworkSecurityEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:NetworkSecurityEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Network_Security_Equipment"
  },
  "https://w3id.org/rec#OccupancySensorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:OccupancySensorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Occupancy_Sensor_Equipment"
  },
  "https://w3id.org/rec#PeopleCountSensorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:PeopleCountSensorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#People_Count_Sensor_Equipment"
  },
  "https://w3id.org/rec#SensorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:SensorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Sensor_Equipment"
  },
  "https://w3id.org/rec#Server": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:Server",
    "replacement": "https://brickschema.org/schema/Brick#Server"
  },
  "https://w3id.org/rec#ThermostatEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:ThermostatEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Thermostat"
  },
  "https://w3id.org/rec#VibrationSensorEquipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:VibrationSensorEquipment",
    "replacement": "https://brickschema.org/schema/Brick#Vibration_Sensor_Equipment"
  },
  "https://w3id.org/rec#WirelessAccessPoint": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:WirelessAccessPoint",
    "replacement": "https://brickschema.org/schema/Brick#Wireless_Access_Point"
  },
  "https://brickschema.org/schema/Brick#Atrium": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Atrium",
    "replacement": "https://w3id.org/rec#Atrium"
  },
  "https://brickschema.org/schema/Brick#Auditorium": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Auditorium",
    "replacement": "https://w3id.org/rec#Auditorium"
  },
  "https://brickschema.org/schema/Brick#Basement": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:BasementLevel",
    "replacement": "https://w3id.org/rec#BasementLevel"
  },
  "https://brickschema.org/schema/Brick#Battery_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ElectricityRoom",
    "replacement": "https://w3id.org/rec#ElectricityRoom"
  },
  "https://brickschema.org/schema/Brick#Bench_Space": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider creating a rec:Zone that is part of a rec:Stadium",
    "replacement": "https://w3id.org/rec#Zone"
  },
  "https://brickschema.org/schema/Brick#Broadcast_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:RecordingRoom",
    "replacement": "https://w3id.org/rec#RecordingRoom"
  },
  "https://brickschema.org/schema/Brick#Cafeteria": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:CafeteriaRoom",
    "replacement": "https://w3id.org/rec#CafeteriaRoom"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Discharge_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Discharge_Flow_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Flow_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Discharge_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Return_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Chilled_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Return_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Chilled_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Supply_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Supply_Flow_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Flow_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Chilled_Water_Supply_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Cold_Box": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Laboratory",
    "replacement": "https://w3id.org/rec#Laboratory"
  },
  "https://brickschema.org/schema/Brick#Concession": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:FoodHandlingRoom",
    "replacement": "https://w3id.org/rec#FoodHandlingRoom"
  },
  "https://brickschema.org/schema/Brick#Condenser": {
    "version": "1.3.0",
    "message": "'Condenser' and 'Condensing Unit' are interchangable terms. Renaming class to 'Condensing_Unit' to further aligns with ASHRAE's terminology.",
    "replacement": "https://brickschema.org/schema/Brick#Condensing_Unit"
  },
  "https://brickschema.org/schema/Brick#Conference_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ConferenceRoom",
    "replacement": "https://w3id.org/rec#ConferenceRoom"
  },
  "https://brickschema.org/schema/Brick#Control_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:SecurityRoom",
    "replacement": "https://w3id.org/rec#SecurityRoom"
  },
  "https://brickschema.org/schema/Brick#Copy_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:CopyingRoom",
    "replacement": "https://w3id.org/rec#CopyingRoom"
  },
  "https://brickschema.org/schema/Brick#Cubicle": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Workspace perhaps with a rec:Desk",
    "replacement": "https://w3id.org/rec#Workspace"
  },
  "https://brickschema.org/schema/Brick#Differential_Discharge_Return_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Differential_Entering_Leaving_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Differential_Supply_Return_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Differential_Entering_Leaving_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Discharge_Chilled_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water"
  },
  "https://brickschema.org/schema/Brick#Discharge_Chilled_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Discharge_Condenser_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water"
  },
  "https://brickschema.org/schema/Brick#Discharge_Condenser_Water_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Discharge_Condenser_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Discharge_Condenser_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Discharge_Hot_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Hot_Water"
  },
  "https://brickschema.org/schema/Brick#Discharge_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water"
  },
  "https://brickschema.org/schema/Brick#Domestic_Hot_Water_Discharge_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Domestic_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Domestic_Hot_Water_Discharge_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Domestic_Hot_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Domestic_Hot_Water_Supply_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Domestic_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Domestic_Hot_Water_Supply_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Domestic_Hot_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Effective_Air_Temperature_Cooling_Setpoint": {
    "version": "1.3.0",
    "message": "The class 'Effective_Air_Temperature_Cooling_Setpoint' is deprecated in favor of further specifying that it is a zone air setpoint.",
    "replacement": "https://brickschema.org/schema/Brick#Effective_Cooling_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Effective_Air_Temperature_Heating_Setpoint": {
    "version": "1.3.0",
    "message": "The class 'Effective_Air_Temperature_Heating_Setpoint' is deprecated in favor of further specifying that it is a zone air setpoint.",
    "replacement": "https://brickschema.org/schema/Brick#Effective_Heating_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Effective_Zone_Air_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "The class 'Effective_Zone_Air_Temperature_Setpoint' is deprecated and replaced to better represent its function as a target setpoint",
    "replacement": "https://brickschema.org/schema/Brick#Effective_Target_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Employee_Entrance_Lobby": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ServiceEntrance",
    "replacement": "https://w3id.org/rec#ServiceEntrance"
  },
  "https://brickschema.org/schema/Brick#Energy_Zone": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Zone",
    "replacement": "https://w3id.org/rec#Zone"
  },
  "https://brickschema.org/schema/Brick#Entrance": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Entrance",
    "replacement": "https://w3id.org/rec#Entrance"
  },
  "https://brickschema.org/schema/Brick#Equipment_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:UtilitiesRoom",
    "replacement": "https://w3id.org/rec#UtilitiesRoom"
  },
  "https://brickschema.org/schema/Brick#Exercise_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ExerciseRoom",
    "replacement": "https://w3id.org/rec#ExerciseRoom"
  },
  "https://brickschema.org/schema/Brick#Exhaust_Fan_Disable_Command": {
    "version": "1.3.0",
    "message": "Exhaust_Fan_Disable_Command is deprecated as a point name should not include more specific equipment names than top level equipment names",
    "replacement": "https://brickschema.org/schema/Brick#Disable_Command"
  },
  "https://brickschema.org/schema/Brick#Exhaust_Fan_Enable_Command": {
    "version": "1.3.0",
    "message": "Exhaust_Fan_Enable_Command is deprecated as a point name should not include more specific equipment names than top level equipment names",
    "replacement": "https://brickschema.org/schema/Brick#Enable_Command"
  },
  "https://brickschema.org/schema/Brick#Fire_Zone": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ServiceEntrance",
    "replacement": "https://w3id.org/rec#ServiceEntrance"
  },
  "https://brickschema.org/schema/Brick#Fresh_Air_Fan": {
    "version": "1.3.0",
    "message": "Fresh Air Fan is deprecated in favor of Outside Fan because the latter is a more accurate representation",
    "replacement": "https://brickschema.org/schema/Brick#Outside_Fan"
  },
  "https://brickschema.org/schema/Brick#Generator_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ElectricityRoom",
    "replacement": "https://w3id.org/rec#ElectricityRoom"
  },
  "https://brickschema.org/schema/Brick#HVAC_Zone": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:HVACZone",
    "replacement": "https://w3id.org/rec#HVACZone"
  },
  "https://brickschema.org/schema/Brick#Hallway": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Hallway",
    "replacement": "https://w3id.org/rec#Hallway"
  },
  "https://brickschema.org/schema/Brick#Heat_Exchanger_Discharge_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Heat_Exchanger_Leaving_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Heat_Exchanger_Supply_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Heat_Exchanger_Leaving_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Heat_Sensor": {
    "version": "1.4.0",
    "message": "This class has a poor definition is supplanted by Temperature_Sensor",
    "replacement": "https://brickschema.org/schema/Brick#Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#High_Temperature_Hot_Water_Discharge_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_High_Temperature_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#High_Temperature_Hot_Water_Return_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_High_Temperature_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#High_Temperature_Hot_Water_Supply_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_High_Temperature_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Discharge_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Hot_Water_Leaving_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Discharge_Flow_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Hot_Water_Leaving_Flow_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Return_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Hot_Water_Entering_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Supply_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Hot_Water_Leaving_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Supply_Flow_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Hot_Water_Leaving_Flow_Setpoint"
  },
  "https://brickschema.org/schema/Brick#IDF": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:CableRoom",
    "replacement": "https://w3id.org/rec#CableRoom"
  },
  "https://brickschema.org/schema/Brick#Janitor_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:BackOffice",
    "replacement": "https://w3id.org/rec#BackOffice"
  },
  "https://brickschema.org/schema/Brick#Library": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Library",
    "replacement": "https://w3id.org/rec#Library"
  },
  "https://brickschema.org/schema/Brick#Light_Command": {
    "version": "1.3.1",
    "message": "Replaced with Lighting_Command to represent its function more precisely.",
    "replacement": "https://brickschema.org/schema/Brick#Lighting_Level_Command"
  },
  "https://brickschema.org/schema/Brick#MDF": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:CableRoom",
    "replacement": "https://w3id.org/rec#CableRoom"
  },
  "https://brickschema.org/schema/Brick#Mail_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:MailRoom",
    "replacement": "https://w3id.org/rec#MailRoom"
  },
  "https://brickschema.org/schema/Brick#Massage_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:TherapyRoom",
    "replacement": "https://w3id.org/rec#TherapyRoom"
  },
  "https://brickschema.org/schema/Brick#Medium_Temperature_Hot_Water_Discharge_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Medium_Temperature_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Medium_Temperature_Hot_Water_Return_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Medium_Temperature_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Medium_Temperature_Hot_Water_Supply_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Medium_Temperature_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Occupied_Air_Temperature_Cooling_Setpoint": {
    "version": "1.3.0",
    "message": "'Occupied_Air_Temperature_Cooling_Setpoint' is deprecated in favor of further specifying that it is a zone air setpoint.",
    "replacement": "https://brickschema.org/schema/Brick#Occupied_Cooling_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Occupied_Air_Temperature_Heating_Setpoint": {
    "version": "1.3.0",
    "message": "'Occupied_Air_Temperature_Heating_Setpoint' is deprecated in favor of further specifying that it is a zone air setpoint.",
    "replacement": "https://brickschema.org/schema/Brick#Occupied_Heating_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Occupied_Zone_Air_Temperaure_Setpoint": {
    "version": "1.3.0",
    "message": "'Occupied_Zone_Air_Temperature_Setpoint' is deprecated in favor of further specifying that it is a target setpoint",
    "replacement": "https://brickschema.org/schema/Brick#Occupied_Target_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Office_Kitchen": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Kitchenette",
    "replacement": "https://w3id.org/rec#Kitchenette"
  },
  "https://brickschema.org/schema/Brick#Open_Office": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:OfficeLandscape",
    "replacement": "https://w3id.org/rec#OfficeLandscape"
  },
  "https://brickschema.org/schema/Brick#Parking_Space": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ParkingSpace",
    "replacement": "https://w3id.org/rec#ParkingSpace"
  },
  "https://brickschema.org/schema/Brick#Plumbing_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:UtilitiesRoom",
    "replacement": "https://w3id.org/rec#UtilitiesRoom"
  },
  "https://brickschema.org/schema/Brick#Portfolio": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Portfolio",
    "replacement": "https://w3id.org/rec#Portfolio"
  },
  "https://brickschema.org/schema/Brick#Private_Office": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Office",
    "replacement": "https://w3id.org/rec#Office"
  },
  "https://brickschema.org/schema/Brick#Reception": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Reception",
    "replacement": "https://w3id.org/rec#Reception"
  },
  "https://brickschema.org/schema/Brick#Retail_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:RetailRoom",
    "replacement": "https://w3id.org/rec#RetailRoom"
  },
  "https://brickschema.org/schema/Brick#Return_Chilled_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Chilled_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Return_Condenser_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Condenser_Water"
  },
  "https://brickschema.org/schema/Brick#Return_Condenser_Water_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Condenser_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Return_Condenser_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Condenser_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Return_Condenser_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Condenser_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Return_Hot_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Hot_Water"
  },
  "https://brickschema.org/schema/Brick#Return_Hot_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Hot_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Return_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Water"
  },
  "https://brickschema.org/schema/Brick#Rooftop": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:RoofLevel",
    "replacement": "https://w3id.org/rec#RoofLevel"
  },
  "https://brickschema.org/schema/Brick#Server_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:DataServerRoom",
    "replacement": "https://w3id.org/rec#DataServerRoom"
  },
  "https://brickschema.org/schema/Brick#Shared_Office": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:OfficeLandscape",
    "replacement": "https://w3id.org/rec#OfficeLandscape"
  },
  "https://brickschema.org/schema/Brick#Shower": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ShowerRoom",
    "replacement": "https://w3id.org/rec#ShowerRoom"
  },
  "https://brickschema.org/schema/Brick#Solar_Radiance_Sensor": {
    "version": "1.3.0",
    "message": "The class 'Solar_Radiance_Sensor' is deprecated in favor of 'Solar_Irradiance_Sensor'. The new name better reflects the standard unit of measurement, watts per square meter (W/m\u00b2), and aligns with the terminology commonly used in solar applications.",
    "replacement": "https://brickschema.org/schema/Brick#Solar_Irradiance_Sensor"
  },
  "https://brickschema.org/schema/Brick#Staircase": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Stairwell",
    "replacement": "https://w3id.org/rec#Stairwell"
  },
  "https://brickschema.org/schema/Brick#Studio": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:RecordingRoom",
    "replacement": "https://w3id.org/rec#RecordingRoom"
  },
  "https://brickschema.org/schema/Brick#Supply_Chilled_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water"
  },
  "https://brickschema.org/schema/Brick#Supply_Chilled_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Chilled_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Supply_Condenser_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water"
  },
  "https://brickschema.org/schema/Brick#Supply_Condenser_Water_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Supply_Condenser_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Supply_Condenser_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Condenser_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Supply_Hot_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Hot_Water"
  },
  "https://brickschema.org/schema/Brick#Supply_Water": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water"
  },
  "https://brickschema.org/schema/Brick#Switch_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:DataServerRoom",
    "replacement": "https://w3id.org/rec#DataServerRoom"
  },
  "https://brickschema.org/schema/Brick#Team_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:TeamRoom",
    "replacement": "https://w3id.org/rec#TeamRoom"
  },
  "https://brickschema.org/schema/Brick#Trace_Heat_Sensor": {
    "version": "1.4.0",
    "message": "Removed due to unclear definition",
    "replacement": "https://brickschema.org/schema/Brick#Sensor"
  },
  "https://brickschema.org/schema/Brick#Transformer_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:UtilitiesRoom",
    "replacement": "https://w3id.org/rec#UtilitiesRoom"
  },
  "https://brickschema.org/schema/Brick#Unoccupied_Air_Temperature_Cooling_Setpoint": {
    "version": "1.3.0",
    "message": "'Unoccupied_Air_Temperature_Cooling_Setpoint' is deprecated in favor of further specifying that it is a zone air setpoint.",
    "replacement": "https://brickschema.org/schema/Brick#Unoccupied_Cooling_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Unoccupied_Air_Temperature_Heating_Setpoint": {
    "version": "1.3.0",
    "message": "'Unoccupied_Air_Temperature_Heating_Setpoint' is deprecated in favor of further specifying that it is a zone air setpoint.",
    "replacement": "https://brickschema.org/schema/Brick#Unoccupied_Heating_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Unoccupied_Zone_Air_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "'Unoccupied_Zone_Air_Temperature_Setpoint' is deprecated in favor of further specifying that it is a target setpoint",
    "replacement": "https://brickschema.org/schema/Brick#Unoccupied_Target_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Visitor_Lobby": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Lobby",
    "replacement": "https://w3id.org/rec#Lobby"
  },
  "https://brickschema.org/schema/Brick#Wardrobe": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:CloakRoom",
    "replacement": "https://w3id.org/rec#CloakRoom"
  },
  "https://brickschema.org/schema/Brick#Waste_Storage": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:WasteManagementRoom",
    "replacement": "https://w3id.org/rec#WasteManagementRoom"
  },
  "https://brickschema.org/schema/Brick#Workshop": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Workshop",
    "replacement": "https://w3id.org/rec#Workshop"
  },
  "https://brickschema.org/schema/Brick#Zone_Air_Cooling_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "'Zone_Air_Cooling_Temperature_Setpoint' is deprecated to support new naming convention, which reorders intended behaviour (cooling) before the substance (zone air).",
    "replacement": "https://brickschema.org/schema/Brick#Cooling_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Zone_Air_Heating_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "'Zone_Air_Heating_Temperature_Setpoint' is deprecated to support new naming convention, whic reorders intended behaviour (heating) before the substance (zone air)",
    "replacement": "https://brickschema.org/schema/Brick#Heating_Zone_Air_Temperature_Setpoint"
  },
  "https://w3id.org/rec#ICTRack": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:ICT_Rack",
    "replacement": "https://brickschema.org/schema/Brick#ICT_Rack"
  },
  "https://w3id.org/rec#ICT_Equipment": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:ICT_Equipment",
    "replacement": "https://brickschema.org/schema/Brick#ICT_Equipment"
  },
  "https://w3id.org/rec#ICT_Hardware": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:ICT_Hardware",
    "replacement": "https://brickschema.org/schema/Brick#ICT_Hardware"
  },
  "https://w3id.org/rec#Network_Router": {
    "version": "1.4.0",
    "message": "REC ICT classes are being phased out in favor of Brick classes. For a replacement, consider brick:NetworkRouter",
    "replacement": "https://brickschema.org/schema/Brick#Network_Router"
  },
  "https://brickschema.org/schema/Brick#Breakroom": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:StaffRoom",
    "replacement": "https://w3id.org/rec#StaffRoom"
  },
  "https://brickschema.org/schema/Brick#Discharge_Hot_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Hot_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Elevator_Space": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ElevatorShaft",
    "replacement": "https://w3id.org/rec#ElevatorShaft"
  },
  "https://brickschema.org/schema/Brick#Food_Service_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:FoodHandlingRoom",
    "replacement": "https://w3id.org/rec#FoodHandlingRoom"
  },
  "https://brickschema.org/schema/Brick#Furniture": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Furniture",
    "replacement": "https://w3id.org/rec#Furniture"
  },
  "https://brickschema.org/schema/Brick#Lounge": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Lounge",
    "replacement": "https://w3id.org/rec#Lounge"
  },
  "https://brickschema.org/schema/Brick#Mechanical_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:UtilitiesRoom",
    "replacement": "https://w3id.org/rec#UtilitiesRoom"
  },
  "https://brickschema.org/schema/Brick#Medical_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:HealthcareRoom",
    "replacement": "https://w3id.org/rec#HealthcareRoom"
  },
  "https://brickschema.org/schema/Brick#Region": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Region",
    "replacement": "https://w3id.org/rec#Region"
  },
  "https://brickschema.org/schema/Brick#Rest_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:RestingRoom",
    "replacement": "https://w3id.org/rec#RestingRoom"
  },
  "https://brickschema.org/schema/Brick#Security_Service_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:SecurityRoom",
    "replacement": "https://w3id.org/rec#SecurityRoom"
  },
  "https://brickschema.org/schema/Brick#Storey": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Level",
    "replacement": "https://w3id.org/rec#Level"
  },
  "https://brickschema.org/schema/Brick#Supply_Hot_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Hot_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Supply_Water_Flow_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water_Flow_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Break_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:StaffRoom",
    "replacement": "https://w3id.org/rec#StaffRoom"
  },
  "https://brickschema.org/schema/Brick#Discharge_Water_Flow_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water_Flow_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Distribution_Frame": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:CableRoom",
    "replacement": "https://w3id.org/rec#CableRoom"
  },
  "https://brickschema.org/schema/Brick#Elevator_Shaft": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ElevatorShaft",
    "replacement": "https://w3id.org/rec#ElevatorShaft"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Discharge_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Return_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Lobby": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Lobby",
    "replacement": "https://w3id.org/rec#Lobby"
  },
  "https://brickschema.org/schema/Brick#Restroom": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Bathroom",
    "replacement": "https://w3id.org/rec#Bathroom"
  },
  "https://brickschema.org/schema/Brick#Return_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Site": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Site",
    "replacement": "https://w3id.org/rec#Site"
  },
  "https://brickschema.org/schema/Brick#Storage_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Storage",
    "replacement": "https://w3id.org/rec#Storage"
  },
  "https://brickschema.org/schema/Brick#Building": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Building",
    "replacement": "https://w3id.org/rec#Building"
  },
  "https://brickschema.org/schema/Brick#Discharge_Water_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Electrical_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:ElectricityRoom",
    "replacement": "https://w3id.org/rec#ElectricityRoom"
  },
  "https://brickschema.org/schema/Brick#Enclosed_Office": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Worksapce",
    "replacement": "https://w3id.org/rec#Workspace"
  },
  "https://brickschema.org/schema/Brick#Hot_Water_Supply_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Hot_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Office": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Office",
    "replacement": "https://w3id.org/rec#Office"
  },
  "https://brickschema.org/schema/Brick#Return_Water_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Return_Water_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Entering_Water_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Service_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:UtilitiesRoom",
    "replacement": "https://w3id.org/rec#UtilitiesRoom"
  },
  "https://brickschema.org/schema/Brick#Supply_Water_Flow_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water_Flow_Sensor"
  },
  "https://brickschema.org/schema/Brick#Laboratory": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Laboratory",
    "replacement": "https://w3id.org/rec#Laboratory"
  },
  "https://brickschema.org/schema/Brick#Outdoor_Area": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:OutdoorSpace",
    "replacement": "https://w3id.org/rec#OutdoorSpace"
  },
  "https://brickschema.org/schema/Brick#Telecom_Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:DataServerRoom",
    "replacement": "https://w3id.org/rec#DataServerRoom"
  },
  "https://brickschema.org/schema/Brick#Discharge_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Zone_Air_Temperature_Setpoint": {
    "version": "1.3.0",
    "message": "The class 'Zone_Air_Temperature_Setpoint' is deprecated in favor of more explicit class names to distinguish target and cooling/heating setpoints.",
    "replacement": "https://brickschema.org/schema/Brick#Target_Zone_Air_Temperature_Setpoint"
  },
  "https://brickschema.org/schema/Brick#Common_Space": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Space",
    "replacement": "https://w3id.org/rec#Space"
  },
  "https://brickschema.org/schema/Brick#Supply_Water_Temperature_Sensor": {
    "version": "1.3.0",
    "message": "Swapped supply/return for entering/leaving with water-related points",
    "replacement": "https://brickschema.org/schema/Brick#Leaving_Water_Temperature_Sensor"
  },
  "https://brickschema.org/schema/Brick#Zone": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Zone",
    "replacement": "https://w3id.org/rec#Zone"
  },
  "https://brickschema.org/schema/Brick#Floor": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Level",
    "replacement": "https://w3id.org/rec#Level"
  },
  "https://brickschema.org/schema/Brick#Space": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Space",
    "replacement": "https://w3id.org/rec#Space"
  },
  "https://brickschema.org/schema/Brick#Location": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Architecture",
    "replacement": "https://w3id.org/rec#Architecture"
  },
  "https://brickschema.org/schema/Brick#Room": {
    "version": "1.4.0",
    "message": "Brick location classes are being phased out in favor of RealEstateCore classes. For a replacement, consider rec:Room",
    "replacement": "https://w3id.org/rec#Room"
  }
}

来源:Brick Schema 官方版本发布 · github.com